Question
What Is Extended Entry In Keyscan Aurora?
Answer
Extended Entry is a feature in Aurora that allows a panel to signal a door operator to follow a system unlock on valid credential reads and requests to exit
KC panels currently do not support Extended Entry (in development)
When Is Extended Entry Used?
Extended Entry is used when a door operator needs to follow the door unlock via a credential read or RTE trigger
Can be used whenever there is a need for a relay that follows the door unlock via a credential read or RTE trigger
When Is Extended Entry Not A Good Solution?
If the door is on a schedule, then the Extended Entry is not going to work with the RTE input
Adding an external relay (eg: RCI RB-DPDT8A) to the door lock relay for a DPDT connection to both the lock & the operator is a better solution
How Is Extended Entry Setup?
Extended Entry requires setup at the hardware and in the Software.
Hardware
CA150 requires S1.8 ON, to toggle the Auxiliary Output relay into an Extended Entry relay
CA250 uses the OCB8 on Control 1 for its Extended Entry relays (relays 5 & 6)
CA4500 requires an OCB8 connected to Control 4, which will follow the door relays connected to Control 1
CA8500 requires an OCB8 connected to Control 4, which will follow the door relays connected to Control 1
Software
Door Relay Follower
The Doors screen (in Hardware Setup) has a Door Relay Follower setting which gives the option of firing the designated Extended Entry relay simultaneously with its corresponding door output relay
The Door Relay Follower option is located in the Extended Entry Door Held Open field, below 99
Works with all CA panels
Edit Person - Extended Entry
The Extended Entry setting on the Edit Person screen enables the presentation of a credential to cause the access control system to invoke the Extended Entry Timer and Extended Entry Door Held Open settings. These two settings are adjusted in the Hardware Setup screen
This setting affects all credentials assigned to the person
Works with all CA panels
Extended Entry Relay All Cards Enabled
This setting is found on the Additional Settings screen in Hardware Setup
This feature enables the presentation of a credential to cause the access control system to invoke the Extended Entry Timer and Extended Entry Door Held Open settings. These two settings are adjusted in the Hardware Setup screen
Works with CA250, CA4500 & CA8500
How Is Extended Entry Wired?
Wiring diagrams are located in the following article: Keyscan CA/EC Series Documentation
Review the corresponding (11x17) document(s)