Overview
The SL30DBL is supplied with a 7-way wire loom that plugs directly into the lock. The wires are color coded
as per table below, with the power and control wires being essential connections and the four monitor
connections being optional.
| Wire Colour | Meaning | Description |
|---|---|---|
| RED | Power Supply (12 - 24VDC) | Positive connection to DC power supply |
| BLACK | Negative connection to DC power supply | |
| BLUE | Control | Switched positive control input |
| VIOLET | Bolt Position Monitor | Normally open contact (NO), closed when the bolt pin is extended (optional) |
| WHITE | Door Position Monitor | Normally open contact (NO), closed when the strike is aligned with the lock (optional) |
Fail Safe Connection
When in Fail Safe configuration, applying positive voltage to the control wire triggers the SL30DBL to lock
(active-high locking signal). In the event of a power cut, the SL30DBL will unlock.
Fail Secure Connection
When in Fail Secure configuration, applying positive voltage to the control wire triggers the SL30DBL to unlock
(active-low locking signal). In the event of a power cut, the SL30DBL will remain locked.