YD30D Double Sideload Lock Technical Data and Pre-Installation Assessment
YD30D Double Sideload Lock Mortise Installation
YD30D Double Sideload Lock Surface Mounting Installation
YD30D Double Sideload Lock Wiring
YD30D Double Sideload Lock Operating Mode
YD30D Double Sideload Lock Maintenance
YD30D Installation & Operating Instructions
Contents and Purpose
This document describes the installation, connection, operation, and maintenance of the lock SL30DBL. Read the document carefully and observe the instructions it contains. They contain important information for reliable installation and trouble-free operation.
Target Group
Target group of these instructions are:
• Installer
• Service Technician
Installers and service technicians are skilled personnel who have the specialist knowledge required for installation, commissioning, and maintenance.
Safety Information
WARNINGS
• Live parts inside.
• The handling and installation of this device is recommended for a professional.
• Use of an unsuitable power supply unit may cause product failure or injury.
• Do not remove the cover plates or face plate.
• Ensure installation does not expose sharp edges of the product to users.
UL REQUIREMENTS
• If the unit is installed on a fire exit door the product installation shall be allowed only if accepted by a local AHJ authority having jurisdiction and comply with NFPA 101.
• The unit is to be connected and controlled via a UL 294 or FWAX7 listed Access Control Unit.
• That the unit shall be installed in accordance with NFPA 70 along with any additional requirements imposed by the local authority of jurisdiction.
• Do not connect the unit to a receptacle controller by a switch.
• If the unit is installed in conjunction with panic hardware the lock shall be installed in a manner to not impair panic device operations.
• The unit shall be powered by a UL 294 or UL 2610 listed power supply with a Class 2 power limited output.
• All factory tested grades were not evaluated by UL.
• UL1034 rating only applies when product is installed in a mortised application.
• UL10C rating only applies when product is installed in the vertical position.
Regulatory Compliance Information
This product is in compliance with the CE Directives including Electromagnetic Compatibility (EMC) Directive, Restriction of the use of certain hazardous substances (RoHS) Directive, and Registration, Evaluation, Authorization and Restriction of Chemicals (REACH) Regulation.
This product is in compliance with the United Kingdom (UK) Legislation including the Electromagnetic Compatibility Regulation 2016, and the Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012.
CE and UKCA Declaration of Conformity is available at www.dormakaba.com.
| EN14846:2008 | ||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
| 3 | X | 9 | 0* | / | G | 2 | 1 | 1 |
*Grade 0 for classification 4 ‘Suitability for use on fire/smoke doors’ applies only to the product when used as a primary latching device for a fire/smoke door. The product is suitable for use on a fire/smoke door when installed as an auxiliary locking device alongside a primary latching device with appropriate test evidence.
This appliance is labelled in accordance with European Directive 2012/19/EU concerning used electrical and electronic appliances (waste electrical and electronic equipment - WEEE). The guideline determines the framework for the return and recycling of used appliances as applicable throughout the EU.
In Countries Outside the European Union and EEA (Norway, Iceland, and Liechtenstein): If you wish to dispose of this product, please contact your local authorities and ask for the correct way of disposal.
This product is in compliance with the Regulatory Compliance Mark (RCM) for Australia and New Zealand.
This product is regulated by the UL/CSA and bears UL/C-UL certification.
Certifications: UL294, UL1034, ULC-S533-15
UL File Number: BP7604, R22400
UL Categories: CVXY, ALVY, FWAX7, GWXT
| UL294 | Line Security Level I Standby Power Level I Attack Level I Endurance Level IV |
| UL1034 | Static Strength: 1,500 lbf (6,673N) Dynamic Strength: 70 ft·lbf (95J) Endurance: 250,000 cycles |
| UL10C | For use in vertical orientation with any UL swinging type fire door frame rated up to and including 3 hours. |
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a residential, commercial, or industrial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
Modifications: Any modifications made to this device that are not approved by the manufacturer may void the authority granted to the user by the FCC to operate this equipment.
Innovation, Science and Economic Development Canada ICES-003:
CAN ICES-3(B)/NMB-3(B)